Cable Design
User Guide
Cable Routing Rules
: Rule One
Rule One
When a cable is routed from or to:
1
Source connection, equipment or electrical connection
2, 4, 6, 8
Entry into a cableway
3, 5, 7, 9
Exit from a cableway
10
Destination connection, equipment or electrical connection.
Note:
When connected to equipment, elconn may not have a direction.
The cable will have a minimum straight length in the same direction as the connection point:
•
If the cable has a bend radius greater than 0, then the bend radius for a metric project is plus 10mm or 1/2” for an imperial project.
•
If the bend radius is equal to 0, then the bend radius for metric project is 100mm or 4” for an imperial project.